PV500-22A 08-98 1 Section 22A INSTALLATION & MAINTENANCE MANUAL FOR PVI FIREPOWER B40 OIL BURNER 1.0 thru 10.0 gph CARBON MONOXIDE WARNING:
PV500-22A 08-98 10 Section 22A PVI FIREPOWER TROUBLESHOOTING SUGGESTIONS OIL BURNER (con't) 4. OIL FLAME IGNITES, BUT THEN FLAME SAFEGUAR
PV500-22A 08-98 11 Section 22A PVI FIREPOWER TROUBLESHOOTING SUGGESTIONS OIL BURNER (con't) 6. OIL HIGH FIRE INPUT RATE CANNOT BE ACHIEV
PV500-22A 08-98 2 Section 22A PVI FIREPOWER B40 OIL BURNER ELECTRICAL 1. Wiring to the unit should conform to
PV500-22A 08-98 3 Section 22A PVI FIREPOWER B40 OIL BURNER START-UP (Refer to Figure 22-1 to identify burner parts) 1. Remove the enclosure pa
PV500-22A 08-98 4 Section 22A PVI FIREPOWER B40 OIL BURNER START-UP (con't) After purging is complete, terminal 3 energizes the oil valve
PV500-22A 08-98 5 Section 22A PVI FIREPOWER B SERIES OIL BURNER START-UP (con't) 20. Record the following information for future use:
PV500-22A 08-98 6 Section 22A PVI FIREPOWER SINGLE STAGE B SERIES OIL BURNER ADJUSTMENTS AIR ADJUSTMENT Loosen the locking screw and move t
PV500-22A 08-98 7 Section 22A PVI FIREPOWER TWO STAGE B SERIES OIL BURNER ADJUSTMENTS AIR ADJUSTMENT First stage: Set the operating switch
PV500-22A 08-98 8 Section 22A PVI FIREPOWER NOZZLE POSITION INPUT - GPH NOZZLE POSITION 1.4 1 2.8 3 4.3 4 5.7 2 7.2 2 8.6 4 TABLE 22-2
PV500-22A 08-98 9 Section 22A PVI FIREPOWER TROUBLESHOOTING SUGGESTIONS OIL BURNER 1. BURNER FAILS TO START: A. Defective on/off or fuel tra